2026
Autores
Elhawash, AM; Hussein, AS; Araújo, RE; Lopes, JAP;
Publicação
CONTROL ENGINEERING PRACTICE
Abstract
The polarization curve characteristics of proton exchange membrane (PEM) hydrogen electrolyzers lead to large variations in the equivalent load impedance over the operating current range. This results in a varying closed-loop system time response when traditional fixed-gain PI controllers are employed. In this work, the design and experimental validation of a 3-phase interleaved buck converter controlled via a proposed adaptive lead-lag current control strategy for a PEM hydrogen electrolyzer load is presented. The incremental load conductance method is used to obtain a control-oriented model of the converter-electrolyzer system, enabling real-time calculation of controller parameters via pole-zero cancellation and user-specified transient performance. A laboratory prototype is implemented to experimentally verify the approach under step-load changes, ramp-load changes, and 50% input voltage sag conditions. The results show less than 1% current ripple, identical transient performance over the entire operating range, and improved disturbance ride-through performance compared to a traditional PI controller. The proposed approach offers a viable and robust control solution for high-current PEM electrolyzer applications.